变电站断路器更换方法的优化 Replacement Method OptimiTation of the Breakers in Substation.pdf

第 23卷 第 10期 源 技 木 锯 淆 Vo .『23 NO.1O 能源与电力工程 2011年10月 EnergyTechnologyandEconomics 0Ct2011 文章编号:1674—8441(201l、10—0034—03 秦卫东,郭 锐,苏长宝 (河南省电力公司南阳供电公司,河南 南阳 473000) ethodOptimiTationoftheBreakersinSubstation QINWeidong,GUORui,SUChangbao (NanyangPowerSupplyCompanyofHenanElectricCorporation,Nanyang473000,China) Abstract:Alongwithrapiddevelopmentofpowertechnology,theoldprimaryequipmentinmanysubstationsisinthe urgentneedsofreplacement.Asamajorprimaryequipment,thebreakerplaysanimportantroleinstableoperationof asubstation.Thetraditionalbreakerreplacementmethodhasatime—consumingproblem,affectingthepowersupply reliabilitV.Thebreakerreplacementmethodfor110kV substationsisoptimizedinthispaperbyusingthekeyroute method.Itisprovedthattheoptimizednew methodcan significantlyshorten thereplacementtimeandreducethe powercuttimeofatransmissionline,subsequentlyimprovingthestabilityofelectricpowersystem andthereliability ofpowersupply. Keywordm substation;breaker;keyroutemethod;optimization 0 引言 1 传统施工方法的调查 近年来 ,随着 电力事业飞速发展 ,许多变 电站 经调查,传统的更换断路器的方法是先把要更 安装的老式一次设备,存在设备老化 、性能下降的 换的断路器所在的线路停 电,然后拆除老旧设备 , 现象,其可靠性已不能满足电网稳定性的需要。更 经必要的准备后换上新的设备,最后对新设备进行 换老化一次设备 ,提高电网运行可靠性及供电可靠 验收试验,验收试验合格后设备送电、线路投运。 性已成为各电力公司急需解决的问题lll。断路器作为 以110kV变电站为例,采用传统的施工方法更 重要的一次设备,对于变 电站的稳定运行具有重要 换一台 110kV断路器的停电时间为 l3天左右,如 作用 1。在更换断路器的过程中寻求能够缩短线路 图 1所示。传统施工方法更换 110kV断路器,所有 停电时间的方法,可以提高电网的稳定性与可靠性。 工序都是在线路停电的情况下进行的,施工时间和 收稿 日期:2011—05一l8 第10期 秦卫东等:变电站断路器更换方法的优化 能源与电力工程 e 设备停 电—◆ 拆除旧断路器及基础 (4h)-—◆ 图2所示 。 制作新 断路器基础、凝固(平均 12天)—— 安装新断路器 (8h)— · 电气交接试验 (8h)-—◆

您可能关注的文档

文档评论(0)

1亿VIP精品文档

相关文档