- 1、原创力文档(book118)网站文档一经付费(服务费),不意味着购买了该文档的版权,仅供个人/单位学习、研究之用,不得用于商业用途,未经授权,严禁复制、发行、汇编、翻译或者网络传播等,侵权必究。。
- 2、本站所有内容均由合作方或网友上传,本站不对文档的完整性、权威性及其观点立场正确性做任何保证或承诺!文档内容仅供研究参考,付费前请自行鉴别。如您付费,意味着您自己接受本站规则且自行承担风险,本站不退款、不进行额外附加服务;查看《如何避免下载的几个坑》。如果您已付费下载过本站文档,您可以点击 这里二次下载。
- 3、如文档侵犯商业秘密、侵犯著作权、侵犯人身权等,请点击“版权申诉”(推荐),也可以打举报电话:400-050-0827(电话支持时间:9:00-18:30)。
- 4、该文档为VIP文档,如果想要下载,成为VIP会员后,下载免费。
- 5、成为VIP后,下载本文档将扣除1次下载权益。下载后,不支持退款、换文档。如有疑问请联系我们。
- 6、成为VIP后,您将拥有八大权益,权益包括:VIP文档下载权益、阅读免打扰、文档格式转换、高级专利检索、专属身份标志、高级客服、多端互通、版权登记。
- 7、VIP文档为合作方或网友上传,每下载1次, 网站将根据用户上传文档的质量评分、类型等,对文档贡献者给予高额补贴、流量扶持。如果你也想贡献VIP文档。上传文档
查看更多
HVAC Guide Specifications
Variable Speed Screw Chiller
Size Range:
300 to 550 Tons (1055 to 1934 kW) Nominal
Carrier Model Number:
23XRV
Part 1 — General
1.01 SYSTEM DESCRIPTION
A. Microprocessor-controlled liquid chiller shall use a semi-hermetic screw compressor using refrigerant HFC-134a only. Chiller refrigerant shall not have a planned phase out date.
B. If a manufacturer proposes a liquid chiller using HCFC-123 refrigerant, which has a planned phase out date, then the manufacturer shall include in the chiller price:
1. A vapor activated alarm system consisting of all alarms, sensors, safeties, and ventilation equipment as required by ANSI/ASHRAE Standard 15 Safety Code for Mechanical Refrigeration (latest edition) with the quotation. System shall be capable of responding to HCFC-123 levels of 10 ppm Allowable Exposure Limit (AEL).
2. A free-standing refrigerant storage tank and pumpout unit shall be provided. The storage vessels shall be designed per ASME Section VIII Division 1 code with 300 psig (2068 kPa) design pressure. Double relief valves per ANSI/ ASHRAE 15, latest edition, shall be provided. The tank shall include a liquid level gage and pressure gage. The pumpout unit shall use a semi-hermetic reciprocating compressor with water cooled condenser. Condenser water piping, 3-phase motor power, and 115-volt control power shall be installed at the jobsite by the installing contractor.
3. Zero emission purge unit capable of operating even when the chiller is not operating.
4. Back-up relief valve to rupture disk.
5. Factory-installed chiller pressurizing system to prevent leakage of noncondensables into the chiller during shutdown periods.
6. Plant room ventilation.
7. Removal and disposal of refrigerant at the end of the phase out period.
8. Chillers utilizing a purge unit shall include in the machine price the costs to perform the following regular maintenance procedures:
a. Weekly: Check refrigerant charge.
b. Quarterly: Charge purge
您可能关注的文档
最近下载
- 慢性鼻炎中医治疗PPT大纲.pptx VIP
- 2012年度证公司会员经营业绩排名情况.doc VIP
- 2025年最新人教部编数学七年上册全册知识点梳理、归纳 (2套)初一数学期末总复 .pdf VIP
- 智能客服:客服机器人优化_(1).智能客服基础理论.docx VIP
- 小儿感冒的中医内科治疗方法.pptx VIP
- 智能客服系统智能客服系统智能客服机器人智能客服机器人性能优化方案.docx VIP
- Geely Galaxy M9吉利Galaxy M9-2025欧洲车身会议.pdf VIP
- 二手手机交易信用风险预警分析报告.docx
- 2013年度证券公司会员经营业绩排名情况.docx VIP
- 建筑的幕墙工程施工.ppt VIP
原创力文档


文档评论(0)