MM440(国外英文资料)
MM440(国外英文资料)
F0001
Over current
? The power of the motor (P0307) and the frequency conversion
The power of the device (P0206) does not correspond
? The motor cable is too long
? The conductor of the motor shorted
? A ground fault
Check the following:
The power of the motor (P0307) must be the work of the inverter
The rate (P0206) corresponds to that.
The length of the cable shall not exceed the maximum allowable.
There must be no short circuit or no inside motor cable and motor
Ground fault
The motor parameters of the input converter must be used
The motor parameters correspond to each other
The input converters stator resistance (P0350) must be positive
It is correct
The cooling air duct of the motor must be free and the motor is not allowed
load
increases the slope time
reduces the value of promotion
Off2
F0002
overvoltage
? Dc circuit voltage controller is prohibited
(P1240 = 0)
? Voltage of dc loop (r0026) exceeds
The tripping voltage level (P2172)
? The power supply voltage is too high, or electricity
Motivation is caused by regenerative braking mode
Overvoltage.
? The slope falls too fast, or the motor is big
The inertia load drives the spin and is regenerated
Braking.
Check the following:
Power supply voltage (P0210) must be specified in the frequency changer
Within the range.
Dc loop voltage controller must be valid (P1240),
And its parameterized correctly.
Slope descent time (P1121) must be the inertia of the load
Match.
The required braking power must be within the specified limit.
Pay attention to
The greater the inertia of the load, the longer the incline; Shape
The FX and GX converter should be plugged into the brake resistance.
Off2
F0003
Under voltage
? Power failure.
? The impact load exceeds the specified value.
Check the following:
Power supply voltage (P0210) must be specified in the frequency changer
Within the range.
Check whether the power supply is short or instantaneous
Low.
Enable dynamic buffering (P1240 = 2)
Off2
F0004
The frequency co