拉法基水泥集团--设备调试说明30
Test Commissioning
Electrical: Energizing MCC No of pages
/ Equipment Item: Issue Date: 11th Oct., 2008 Rev: R00 Item N°
Sheet No.
Checking before Energizing
送前前检查 Erection
安装 MCC cabinets have been erected ; incoming cables have been test and connected the incoming of MCC
MCC柜已安装完成,MCC进线电缆测试并已连接至MCC进线柜
Earthing system for子MCC is installed
MCC接地系统已完成
Lighting in switch-room is normal operation
电力室内照明已完成
Fire detection system in switch-room is normal operation
火灾报警系统安装已完成
Each emergency Shut-Downs for switch-room has been installed
电力室紧停开关已安装完成
Civil works for switch-room has been finished
电力室土建工程式已完成
□
□
□
□
□
□
Security Check
安全检查 No debris in electrical room,
电力室内无杂物
All feeder of MCC have been take out and locked
MCC所有回路已拉出,并已上锁,
Fire detection system are normal operation;
火灾报警系统已能正常工作;
Lighting is normal operation
照明正常
Earthing for MCC has been finished
MCC接地已完成
Emergency Shut-Down has been erected
紧停开关已安装完成
Necessary warning plates have been erection in the witch-room
必须的警告牌已准备好
The doors for electrical room can be locked
电力室门能够上锁
□
□
□
□
□
□
Electrical check
电气检查
Clean the electrical room, no debris in electrical room,
电力室内清理干净,室内无异物;
Clean the MCC cabinet,
清理MCC柜
Check the cables erection conditions, such as fixed, no mechanical damage, good arrange and seal.
检查电缆接线是否已完成,电缆布置是否合理,电缆排列整齐,固定是否可靠,接线室内是否密封良好
I/O lists between PLC to MCC incoming have been checked.
MCC 进线柜至PLC的I/O点已检查;
Setting value for protection of MCC incoming breaker has been done according to drawings requirement.
MCC进线柜保护设置已根据图纸设定完成
Temporary auxiliary power from ACC and UPS have been normal operation,
临时辅助电源,UPS电源已正常工作
The door of electrical room can be locked
电力室门能够上锁 □
□
□
□
□
□
□
Electrical test
电气测试
Insulation for MCC bar bus and breaker meet the requirement
MCC母线与断路器回路压侧绝缘测试满足要求
Insulation for LV cables meet requirement, the cables connect is correct,
低压动力电缆绝缘满足要求,电缆接线正确
Ensure the Operation of breaker on MCC incoming in normal operation, the status is
文档评论(0)