3.4.2 Laying of Stove Bottom with Clay Brick
1) The bricklaying shall start from the center to both sides by scribing the level line as per the design elevation on the cross central line.
2) Quality Inspection: leveling instrument
Fig. 3.4-3 Schematic Diagram for Sequence of Clay Brickwork
3.4.3 Paving of Fused Sand
1) The dry sand with maximum particle diameter below 5mm shall be paved on the clay bricks according to the design elevation.
2) The large screw rod built around shall be covered with the rainproof cloth and bound tightly with steel wire.
3) This work has something to do with installation of stove shell for Section 1. The stove shell for the 1st section being hoisted, the rainproof cloth shall be removed. Following inspection of stove shell elevation after hoisting, the stove shell for the 1st section shall be hoisted again to inspect whether the surface of fused sand has the drop pit. If there is the drop pits, they shall be re-leveled with fused sand. Such an inspection shall be repeated until the flatness is competent.
3.4.4 Packing of Water-free Tamping
After the stove shell for the 3rd section is installed, the explosive shall be packed with tamping. The tamping shall be pressed to pack the lower part of the stove shell. And the redbrick shall be laid close to the stove shell to block off the water-free tamping. The surface of redbrick shall be plastered with a 20mm-thick layer of 1:2 cement mortar.
3.4.5 Pressure Grouting
1) Following the welding of strengthening ring and beam on the lower part of stove shell and the fastening of bolts, the pressure grouting can start after the stove shell is installed to the 6th section. Prior to hoisting of the stove bottom shell, the stub pipe shall be welded and embedded.
Fig. 3.4-4 Schematic Diagram of Grouting Stub Pipe
2) The injection mix is the 425# ordinary Portland cement and the water-cement ratio 0.4~0.5.
3) Before pressure grouting, the grouting holes shall be