PIPING 工程技术标准 2802-CS-PIPING-003 - PAGE 8 - SPECIFICATION FOR 6000T/Y VISCIDITY STABLE FIBER PROJECT PROCESS & UTILITY PIPINGS HOT INSULATION REQUIREMENTS The attached specification ,revised as indicated below, is issued herewith. If this is a later revision than now in your possession,please destroy previous issue. Rev 0 Date 04-06-07 By App Cust App Page Rev Date 04-06-07 By App Cust App Page Rev Date 04-06-07 By App Cust App Page Rev Date 04-06-07 By App Cust App Page Rev Date 04-06-07 By App Cust App Page Note:New issue …………………………………………… Revised sheets only attachde …………………… Entire specification reissued …………………… 保 温 施 工 规 范 (附件2) 1.0 适用范围 本规定适用于管线、塔槽、及设备,其操作温度在60℃以上,650℃ 2.0 一般设计规范 2.1 塔槽、设备及管线的保温度依据厚度表决定之.需要热追踪的管线,除非施工图上有其它注明,否则其保温厚度仍然不变.当操作温度超出保温厚度表内所列温度时,保温的厚度及使用另须依照合约上的规定. 2.2 本规范内的保温材料,适用于操作温度在60℃至650℃ 2.3 管线、塔槽或换热器,须先按“油漆施工规范”做好除锈油底漆工作.其表面如附有油脂、浮灰、污物或水汽湿气时,须处理干净后,始得保温. 2.4 管线、塔槽及设备操作温度在60℃至650℃之间,基于制程需要“温度控制”或为“保护现场工作人员的安全”, 2.5 泵浦和透平机除非需温度控制,否则不需保温。 2.6 管线操作温度超过80℃时,必须在操作人员接近的区域作人员安全保温,安全保温的范围以不超过操作台6尺高或2尺宽的范围为原则.阀类、法兰、由任除非特别注明,否则不需做安全保温.保温设施要求的程度,在施工图中会有所指示,如果有其它实用的保护或遮蔽设施,能保护操作人员的安全,也可以用来代替安全保温 2.7 保温材料必须保持干燥,潮湿时不可用以施工,如果保温材料施工后受潮湿,必须拆除并更换干燥的保温材料.镀锌板在施工前必须特别注意保持干燥,以防止湿气停留于镀锌板的间距中. 2.8 管线、塔槽或设备,须等试压合格后,才可进行保温.未作试压前,若俗先行保温,必须将所有焊口及螺丝露出来,待试压完事后再予以保温。 2.9 保温材料放置时,避免接触不相似的材质,以免产生电化学腐蚀。 2.10直立塔槽壳顶与槽底操作温度有极明显差别,槽的下半部依槽底部的操作温度;槽的上半部依上下部的平均温度作保温处理。保温厚度在塔槽制造图中应详细注明。 保温材料 3.1 保温材料最高使用温度为500℃,所用材料为 3.2 除了阀及管件外,保温之防水金属包覆(详见表3)必须使用0.8mm厚度,915mm宽平板镀锌板。 3.8 使用于塔槽之抗天候包覆(见表3)必须定0.8mm 厚度,915mm宽2440mm长之平板镀锌板。 3.9 除了不锈钢管以外,管线之保温固定线使用#20 BWG之镀锌钢线。保冷及不锈钢管之保温固定则使用#18 BWG之304SS不锈钢线。