ab燃烧炉nh4oh pumpp1842p1843逻辑说明参考t04s05e080ea.pdf

P1842, P1843 Logic Description This is with reference to T04S05E-080EA90-03, “Ammonia Feed Pump Logic”. Note1: (T04S05E-080EA90-03, Grid C-4, E-4) Keep the local control station always in Remote mode when normal operation.(i.e. switch the mode to remote when no site operation) Note2: (T04S05E-080EA90-03, Grid D-2) Precondition for the 2 pumps automatically started by the Pumps outlet pressure low than the setpoint-0.5 MPa(g). That is, only ase of at least 1 pump of the 2 is running, the low pressure interlock is effective. Thi