* * * * * * * * * * * * * * * Electric Resistance Underslab Heating systems must be thermostatically controlled and disabled during summer on-peak periods as defined by the local utility. Evaporator Fans should be variable speed and shall be controlled in response to space conditions. Evaporative Condenser Fans should be variable speed and controlled by condensing temperature. The minimum condensing temperature should be 70 °F. Air-cooled Condenser Fans must be variable speed and controlled by condensing temperature or pressure. The minimum condensing temperature setpoint will be 70 °F or rese