IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 25, NO. 2, JUNE 2010 287 Effect of Voltage and Load Variations on Efficiencies of a Motor-Pump System P. Giridhar Kini, Member, IEEE, and R. C. Bansal, Senior Member, IEEE Abstract—Centrifugal pumps are the most widely used ac- II. METHODOLOGY motor-driven pump systems mainly for water pumping applica- tions. Due to increasing and varying load demand, voltage varia- In order to study the performance variations of a three-phase tion and unbalance is a reality and has to be dealt with carefully. induction motor-pump system for voltage and load variations, Studies on motor-driven systems under conditions of voltage un- the analysis is split into the voltage, motor, and pump side balance have either neglected or maintained constant magnitude of analyses. the rotational loss component and focused only on the motor per- formance while system side performances have not been discussed generally. This paper presents the experimental results of a three- A. Voltage Analysis phase induction motor-pump system subjected to voltage and load Voltage unbalance has been interpreted and mathematically variations with a view to justify that knowledge of voltage and load variations are very much essential for better result analysis. expressed as a voltage unbalance factor (VUF) in a number of ways [8], [12], [15], [18], [21]–[24]. The VUF, as expressed by Index Terms—Centrifugal pump, complex voltage unbalance the International Electrotechnical Commission (IEC), is factor, equal voltage unbalance, overvoltage unbalance,