40UV,UHGuideSpecifications,500to1500RatedCfm.doc

HVAC Guide Specifications Unit Ventilator Size Range: 500 to 1500 Rated Cfm Floor Units (Vertical) 750 to 2000 Rated Cfm Ceiling (Horizontal) Carrier Model Numbers: 40UV (Vertical) 40UH (Horizontal) Part 1 — General 1.01 SYSTEM DESCRIPTION Carrier unit ventilators are designed for floor (vertical) or ceiling (horizontal) mounting. Units shall incorporate chilled water or direct expansion cooling and hot water, steam or electric heat as specified. Units are available with Direct Digital Controls (DDC) that provide stand-alone operation or can be incorporated into Carrier’s i-Vu? Open control system or a BACnet building automation system utilizing the factory-installed Carrier Unit Vent Open Controller. Indoor air quality is assured with dehumidification and ventilation options. 1.02 QUALITY ASSURANCE A. Units shall be tested and certified in accordance with AHRI Standard 840, latest edition. B. Unit shall be constructed and listed in accordance with ETL and ETL, Canada standards (ANSI/UL 1995-1999, second edition) (CAN/CSA C22.2 NO 236-95). C. Unit insulation and adhesive shall meet the requirements for flame spread rating of lower than 25 per ASTM E84 and smoke generation rating of lower than 50 per ASTM E84. Only closed cell insulation shall be used. The use of fiberglass insulation is not acceptable. D. Each coil shall be factory tested for leakage at 350 psig air pressure with coil submerged in water. 1.03 DELIVERY, STORAGE AND HANDLING Units are secured to a heavy-duty wooden pallet, boxed, banded and labeled for shipment. Units must be stored and handled per manufacturer’s recommendations. Part 2 — Equipment 2.01 UNIT DESCRIPTION A. General: The unit shall be a factory-assembled bolt-together unit ventilator. Contained within the unit enclosure shall be factory-installed motor, wiring, blowers, coil(s), bearing, outdoor/return air damper, optional face/bypass damper and optional controls. Unit shall have a draw-thru design for uniform air distribution acr

文档评论(0)

***** + 关注
实名认证
文档贡献者

该用户很懒,什么也没介绍

1亿VIP精品文档

相关文档