有限元法在高压输电线路线夹能量损耗计算中的应用.pdf
第35 卷 第4 期 电 网 技 术 Vol. 35 No. 4
2011 年4 月 Power System Technology Apr. 2011
文章编号:1000-3673 (2011 )04-0218-05 中图分类号:TM 151 文献标志码:A 学科代码:470·4051
有限元法在高压输电线路线夹能量
损耗计算中的应用
厉天威,黄文京,何民,卢本初,薛志方,姚继莎,肖艳玲
(广西电力工业勘察设计研究院,广西壮族自治区南宁市 530023 )
Power Loss Calculation of Clamps for High Voltage Transmission Line by
Finite Element Method
LI Tianwei, HUANG Wenjing, HE Min, LU Benchu, XUE Zhifang, YAO Jisha, XIAO Yanling
(Guangxi Electric Power Industry Investigation Design and Research Institute, Nanning 530023,
Guangxi Zhuang Autonomous Region, China)
ABSTRACT: Improving transmission efficiency of electric 线夹;铸铁线夹
energy and reducing line loss are major energy saving measures, 0 引言
thus it is an important task to reduce the energy consumed by
the fittings for HV transmission lines. To quantitatively analyze 输电线路中常用的线夹分为铸铁线夹和预绞
the energy consumption of fittings, the limitation of solving 式线夹等。铸铁线夹由铸铁材料铸成,预绞式线夹
eddy-current loss of complex-shaped model by analytical 由预绞丝护线条、高强度铝合金护套、橡胶衬垫等
method should be considered. The finite element method is
主要部件构成。由铁磁材料铸成的线夹占线路中线
applied to the modeling of cast iron clamp and the analysis on
eddy-current loss in it. Calculation results conform to the data 夹的大部分,由于铁磁材料的涡流和磁滞作用,每
8 [1]
obtained from tests, so the effectiveness of the proposed 年在输电线路上产生近10 kW⋅h 的能量损耗 。对
method is verified. Applying this method to the calculation of 线夹能量损耗研究的主要困难表现为:由于线夹结
eddy-current loss in pre-twisted suspension clam