增加液氯温度说明书TD200
使用维护手册
——R2.0版——
武汉新世界制冷工业有限公司
2006.09
目 录
一.系统概述····························································2
二.微机箱面板按钮开关、TD200按键的说明················3
三.显示说明····························································5
四.参数设置····························································5
五.基本控制原理·····················································7
六.运行保护····························································9
七.操作示例····························································9
八.安装、接线及调整··············································11
九.常见故障的判别方法··········································13
一.系统概述:
1.用途
建议您先通读《螺杆式制冷压缩机使用维护手册》(以下简称“机组”)总体部分,了解螺杆式制冷压缩机的结构和特性后,将能较容易地理解本《》《》
图 1 微机控制箱面板器件布局示意图
按钮开关说明:
转换开关、按钮开关、急停开关的控制功能详见微机控制箱布置图所示。
SA3——手动、自动选择旋钮,用于选择手动或自动运行方式。
SA4——供液1开关旋钮,用于手动状态时选择供液阀1的状态。
SA5——供液2开关旋钮,用于手动状态时选择供液阀2的状态。
SA8——内压比操作旋钮,用于手动方式下II型压缩机组或低温机组内压比高调节。
SA7——能量位置操作旋钮,用于手动方式下机组的能量调节。
SB2——油泵启动按钮。
SB1——油泵停止按钮。
SB4——压缩机启动按钮。
SB3——压缩机停止按钮。
SB5——报警解除按钮。当机组有报警时按下此按钮可停止报警铃声。
SA2——紧急停止按钮。当机组发生紧急情况时按下此按钮,以停止机组运行。
HL1 、HL2、HL3、HL4、HL5、HL7、HL8、HL9、HL10、HL11——
图 2 TD200 文 本 显 示 器 示 意 图
其中:
▲ : 用于向前切换显示屏或设置数字加键。
▼ : 用于向后切换显示屏或设置数字减键。
ENTER: 用于选择设置参数或回到初始屏显示。
SHIFT: 用于选择对应F5~F8时有效(例F5:先按SHIFT再按F1 即可)。
ESC : 为显示屏功能键,用户不可按该键,若误按后请立即再按一次返回。
F1 ~ F4 : 功能键,分别表示:启动、停止、参数设置、设置确认。
F5 ~ F8 : 功能键(需通过上档键SHIFT来选择),只用于参数设置的确认,即能量和内压比滑阀上、下限的确认。(详见“参数设置”的说明)
注:未经特许的非专业人员,切忌在此面板随意揿动按钮、开关或调整参数值。
三.显示说明
机组运行参数由TD200文本显示屏显示,可显示机组运行中各参数值、报警内容、报警时间、机组运行时间。当微机控制箱接通电源开关,TD200液晶显示屏为初始显示屏,其它屏可通过▲和▼切换。
初始屏(第一屏) 第二屏
第三屏 第四屏
第五屏 第六屏
注:如无液氯温度传感器,则无液氯温度显示。
报警显示屏
若已故障停机,可通过▼键翻阅至报警示屏查看故障原因和故障发生时间。
机组运行时间显示屏
四.参数设置
开放式的参数设置屏专供用户根据工艺要求设定而设计。按F3即可进入参数设置屏,按ENTER移动光标到所需设置参数位置,按▲或▼可设置或修改各参数值(