Inerting
Pulverizer Inerting - Extracts from NFPA 85 2001 Edition
3.8.5.2.3 Normal Shutdown. The requirements in 3.8.5.2.3 shall apply to the removal of coal from service as the only main burner fuel being fired. The requirements in 3.8.5.2.7 shall apply to the removal of coal from service with other fuel remaining in service.
3.8.5.2.3.1 When taking the unit out of service, the boiler load shall be reduced to that necessitating a purge rate airflow using the procedures outlined in 3.8.5.2.3.2 and 3.8.5.2.3.3, while maintaining operation within the tested limits determined in 3.8.5.2.2.5. Prior to removing coal from service and prior to loss of reburn permissives, reburn fuel shall be shut down as defined in 3.6.5.2.9, 3.7.5.2.9, or 3.8.5.2.9.
3.8.5.2.3.2 A pulverized fuel system shall be shut down in the following sequence:
(1) The pulverizer’s fuel input, airflow, and register positions shall be adjusted to values established for start-up.
(2) Igniters shall be placed into service at these burners, when required to maintain flame stability.
(3) The hot primary air shall be shut off and the cold primary air shall be opened to cool down the pulverizer in accordance with Chapter 6.
(4) The feeder shall be stopped in accordance with the manufacturer’s recommendation. Operation of the pulverizer shall be continued with a predetermined airflow prescribed in an established operating procedure that has been proven to be sufficient to empty out the pulverizer and associated burner lines.
(5) The inerting medium shall be introduced into the pulverizer as dictated by the coal characteristics.
(6) The pulverizer subsystem shall be shut down when burner fires are out and the pulverizer is empty and cool.
(7) All individual burner line shutoff valves shall be closed unless otherwise directed by the manufacturer’s instructions.
(8) Igniters shall be removed from service.
3.8.5.2.3.3 As the fuel is reduced, the following procedures shall be followed:
(1) The remaining pulverizers shall b
您可能关注的文档
最近下载
- 初一育才期末数学试卷.docx VIP
- IEC60364554-2021(翻译稿)低压电气装置第554部分电气设备的选择和安装接地配置.pdf VIP
- 11水平五 高一 田径单元18课时计划-《田径:跨栏跑—跨栏步》教案.docx VIP
- 乌兰察布市2025年初中学业水平考试一分一段人数统计表.xlsx VIP
- 职业健康管理要求.docx VIP
- NOK骨架油封样本.pdf VIP
- NB_T 42088-2016继电保护信息系统子站技术规范.pdf
- 抗菌药物临床应用实行分级管理.ppt VIP
- 验房表格精装修详细版.doc VIP
- DB44_T 2746-2025 骨质疏松高风险人群中医健康管理指南.pdf VIP
原创力文档


文档评论(0)