ppt课件-u l f m消防泵系统——syncro弗洛( u l f m fire pump systems- syncro flo).pptVIP

  • 14
  • 0
  • 约 21页
  • 2017-01-09 发布于湖南
  • 举报

ppt课件-u l f m消防泵系统——syncro弗洛( u l f m fire pump systems- syncro flo).ppt

UL/FM Fire Pump Systems Lunch Learn 04/18/05 Rules Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal Split Case Vertical Mounted Split Case Vertical Turbine Compliance to NFPA 20 100% Flow at 100% Head Maximum of 140% of Head at Shutoff Minimum of 65% of Head at 150% of Flow Maximum Allowed Pressure The pump shutoff pressure plus the maximum static suction pressure shall not exceed the pressure for which the system components are rated for. Pressure relief valves shall not be used as a means to meet this requirement. Variable speed pressure limiting control