AV6PLUS旁路系统功能介绍中文版.
功能描述
高压旁路站
HP Bypass Station
Overview (Diagram D)
概述(图标D)
The HP Bypass System consists of the following parts:
高旁由下列部分组成
? Pressure setpoint generation (Diagrams DA/RA)
压力设定值生成(图标DA/RA)
? Pressure controller (Diagram DB/TB)
压力控制器(DB/TB)
? Temperature controller (Diagram DC)
温度控制器(图标DC)
? Spraywater isolation control (Diagram SD)
喷水隔离控制(图标SD)
Pressure setpoint generation
压力设定值生成
2.1 Startup
启动
2.1.1 Mode Selection (Diagram RA)
模式选择(图标RA)
The BP controller is set to “BP auto” by the operator.
旁路控制器被操作员设置成“BP auto”
Operator sets “startup mode ” with “BP start mode on/off” display button.
操作员将“BP Start mode on/off”显示按钮设置为“启动模式”
In “startup mode” the generator it is set to one of the three operating conditions:
在“startup mode”下,生成器被设置成一下三种运行状况:
? Cold start up
冷态启动
? Hot start up
热态启动
? restart
重启
The “cold start up” is active whenever the main steam pressure is below “Pmin”.
当主蒸汽压力低于“Pmin”时冷态启动激活
The “hot start up” is active when the main steam pressure is above “Pmin” and below
“Psync”.
当主蒸汽压力介于Pmin 和Psync时热态启动激活
The “restart” is active when the pressure is above “Pmin” and the BP valve is closed.
当主蒸汽压力高于Pmin且旁路阀关闭时重启模式激活
The signal “cold/hot start up” is generated when the operating “cold start up” or “hot
start up” is on.
当“冷态启动”或者“热态启动”在开位置时产生“冷/热态启动”信号
The “startup mode” is deselected as soon as the pressure reaches “Psync” and the BP
valve is open. The “startup mode” is also deselected when the signal “HP Turbine
loaded” is active or when the pressure controller is switched to manual.
当压力达到Psync且旁路阀打开时,“start up mode”模式失效,当汽机带载信号激活或者压力控制器切换到手动状态时启动模式也失效。
The “fixed pressure mode” is active when the “startup mode” is not on and the
“follow mode“ is not on and the “shut down mode” is not on.
当“startup mode”模式没在开位且“follow mode”未开且“shut down mode”模式也未开时,“fixed pressure mode”定压模式激活
The “follow mode” is active when the BP valve is closed and the DEH signal “HP
Turbine loaded” is active. Further the “follow mode” is active when the signal “Boiler
on” is not on and the
您可能关注的文档
最近下载
- 统编版七年级历史下册第18课《统一多民族国家的巩固和发展》优质教案+导学案(含答案).doc
- 审查调查外查工作培训课件.pdf VIP
- 2024-2025学年初中音乐七年级上册(2024)湘艺版(2024)教学设计合集.docx
- 2024年部编版中考语文模拟试卷及答案.doc VIP
- 《萨班斯法案》课件.ppt VIP
- 2021电子科技大学-计算机体系结构实验报告01.pdf
- 《智能机器人系统》全套教学课件.pptx
- 2023年南京郑和外国语学校小升初分班考试数学模拟试卷及答案解析.pdf
- 统编版七年级历史下册第18课《统一多民族国家的巩固和发展》精美教案+导学案(含答案).doc
- AVL BOOST燃烧及传热模型介绍.pdf VIP
文档评论(0)