冷箱珍珠岩保温处仪表连接要求
PAGE DE GARDE / FRONT PAGE Rev. Date Supervis. Appr. Modifications 0 05.09.94 WEWER Emission Originale/Original Issue
Supersedes RG.321.80
a 02.11.94 WEWER Pages 2,4 to 9 updated b 21.03.97 WEWER Reaffirmed in Microsoft( WORD( c d e f g h i j k l m n p CONTENTS
1 GENERAL : EQUIPMENT GENERAL : EQUIPMENT
Manual Analyses or Sensors
Simple or differential Pressures
Level Gauges on Columns
Gas and Liquid Flowmetering
Gas and Liquid Analyses
Temperature Probes
For standard installation and mounting design refer to GR.350-11 and GR.350-61.
DESIGN OF THE CONNECTIONS
The design is carried out by the piping contractor.
Study of the Routing
The study must be started upon completion of the piping lay-out. It allows : - defining the orientation of the nozzles on the column sections and the casing penetration areas, - -selecting the general option for the routing of the tubes and cables, - -grouping the instrumentation nozzles - -in the special case of tubing for liquid analysis with capillary tube, provide a distance of or = 1000 between the nozzle and the casing wall, if possible (see GR.350.61 mounting 11A).
Collective Routing Principle
The tubes and cables are preferably placed on the inside of the casing wall forming a strand which is held by a stainless steel clip, and come out at the lowest point possible (see chapter 2.3). The routing is traced on a main piping drawing, taking into consideration the following points : - the areas of grouped nozzles, - inspection doors in the casing and ladders on the inside, - casing penetrations.
Routing for connections and casing penetrations.
EXECUTION OF THE CONNECTIONS
Routing
The routing of the tubes and cables consists of :
an individual routing between the nozzle and the casing,
a possible individual routing up to the collective routing,
a collective routing en botte.
Supports of collective routing
Tubes will be installed in c