MARCH 30, 2012 ATTACHMENT PLUGS AND RECEPTACLES - UL 498 119
107 Dielectric Voltage-Withstand Test
107.1 The assembly of a cord and cord connector with pin-type terminals shall be capable of withstanding
without breakdown, for a period of 1 minute, the application of a 60 Hz essentially sinusoidal potential of
1250 V between the two conductors of the flexible cord. Three assemblies are to be selected from the
D
temperature test specified in Temperature Test, Section 104.
o
c
u
107.2 The test potential is to be supplied from a 500 V-A or larger capacity testing transformer whose m
e
output is essentially sinusoidal and can be varied. The applied potential is to be increased from zero until n
t
the required test voltage is reached, and is to be held at that voltage for a period of 1 minute. The increase W
a
in the applied potential is to be at uniform rate and as rapid as is consistent with its value being correctly s