变电站母线接地开关配置的探讨 Approach on the Disposition of Grounding Switches in Substation.pdf

66 变电站母线接地开关配置的探讨 变电站母线接地开关配置的探讨 onthe of SwitchesinSubstation ApproachDispositionGrounding 中山电力设计院有限公司 徐春侠 ElectricPower InstituteCo.Ltd.XuChunxia Zhongshan Design 摘 要:对于屋外配电装置,为保证电气设备和母线的检修安全,应恰当地配置母线接地开关。停电母线上电磁感应 电压,取决于平行带电母线的电流和它们的相对间距。通过实例分析,介绍了确定母线接地开关的安装数量和间距的计算 方法。 Abstract:Toensurethe ofmaintenanceworkandout-door bar switchesshouldbe safety installation,bus power grounding inducedonthe the bus bus currentin live properlyequipped.Theelectromagneticvoltageoutagebar(s)dependsupon nearbyparallel barandtheirrelative acalculation methodfor thelocationandnumberofthe distances.Throughexample,the determinating switchesisintroduced. grounding 关键词:变电站母线电磁感应电压接地开关 words:SubsaionBusbar induced Busbar switch Key Electromagneticvoltage grounding 巾刚分类号:TM564文献标谚:码:B 1.引言 C.相的电流最大时,在A:母线上产生的电磁感应 为保证电气设备和母线的检修安全,变电站 电压最高,其值为: 内每段母线均应装设接地开关或接地器。而对于 x。:。。) (1) 采用双母线接线型式的户外配电装置,当一段母 【,。:=,(x。:c,一丢x。:。厂j1 线停电检修时,另一段相邻平行的运行带电母线 其中, 会通过电磁耦合,在检修母线上产生感应电压。 X』2c1(x_2_I,X』2口1) 因此,母线上接地开关的安装位置和数量,应通 :0.628×10—4(1n—Zl一1) (2) 过在母线上计算的电磁感应电压来确定。 DI 2.母线电磁感应电压的计算 式中,U。:一A:相母线的电磁感应电压(V/m), 作用于停电检修母线上的电磁感应电压可分 I_母线It的三相负荷电流或短路电流(A); 为两类: x脚。一母线llqhA:相对母线I中C.相单位长度的平 1)长期的电磁感应电压,是由运行中的母线 均互感抗(f2/m);抖行母线的长度(m);D.一两 通过正常负荷电流产生的