肯尼亚母线跨线短路动态张力计算

肯尼亚母线跨线短路动态张力计算 工程描述:本期肯尼亚220kV为单母线接线,母线采用双分裂铝绞线型号为2* AAC-800,母线最大跨距34.8m。 Description of the project: 220kv is Single bus connection, the bus is 2* AAC-800, the maximum distance between the bus is 34.8m. 计算依据:IEC_60865-1-1993短路电流效应的计算 The basis of the calculation: calculation of short-circuit current in IEC_60865-1-1993 计算断面及平面图如下: The section and plan of the calculation: 1.1 计算输入参数: 1.1 Common data 220kV三相短路电流: =31.5kA Three-phase initial symmetrical short-circuit current(r.m.s) =31.5kA 短路电流开断时间:T=1s Duration of the first short-circuit current T=1s 母线跨度(考虑绝缘子串长度) l=33.8m Distance between su