- 8
- 0
- 约2.88万字
- 约 64页
- 2018-08-01 发布于贵州
- 举报
变电站电气一次部分初步设计毕业设计(论文)word格式
摘 要
根据设计任务书的要求,本次设计为110kV变电站电气一次部分初步设计,并绘制电气主接线图及其他图纸。该变电站设有两台主变压器,站内主接线分为110kV、35kV和10kV三个电压等级。各个电压等级分别采用单母线分段接线、单母线分段接线和单母线分段接线。
本次设计中进行了电气主接线的设计、短路电流计算、主要电气设备选择及校验(包括断路器、隔离开关、电流互感器、电压互感器、母线等)、各电压等级配电装置设计、直流系统设计以及防雷保护的配置。
关键词:变电站 设计 防雷保护
ABSTRACT
From the guide of engineering design assignment, we have to design primary power-system of 110kV substation and draw main electrical one-line diagram and others. There are two main transformer in the substation in which main electrical connection can be divided into three voltage grades: 110kV, 35kV with 10kV.It deposits sectionalized single bus bar scheme, sectionalized single and sectionalized single bus bar scheme per grade.
There is also a design for main electrical connection in this ngineering, the calculation for short-circuit electric current, the selection of electrical device and calibration (including circuit breaker, isolator, current,transformer, potential transformer ,bus bar etc.) and the design for distribution installation per. voltage grade, direct current system and lightning protection is also included.
Key Words:substation design lightning protection
绪论 1
第1章 变电站总体分析 2
1.1 变电站总体分析 2
第2章 负荷分析计算与主变压器的选择 4
2.1负荷分析计算 4
2.2主变选择 6
2.3 无功补偿 8
第3章 电气主接线设计 11
3.1主接线的设计原则和要求 11
3.2主接线的设计步骤 13
3.3 电气主接线设计 14
第4章 短路电流计算及电气设备选择 16
4.1 短路电流的危害 16
4.2电气设备选择 16
4.3高压断路器的选择 18
4.4隔离开关的选择 19
4.5电压互感器选择 19
4.6电流互感器选择 20
4.7绝缘子和穿墙套管 20
4.8电气设备表 21
第 5 章 配电装置及电气总平面布置设计 23
5.1 概述 23
5.2 配电装置的确定 24
5.3 电气总平面布置 25
第 6 章 防雷保护设计 27
6.1变电站的防雷保护特点 27
6.2变电站直击雷防护 27
6.3侵入波过电压防护 27
第 7 章 避雷针保护范围的计算方法 28
第 8 章 展望………………………… ……………………………………….…….29
致谢 30
参考文献 31
附录Ⅰ 短路电流的计算 32
附录Ⅱ 电气设备的选择 38
附录Ⅲ 避雷针保护范围计算 58绪 论
本文首先根据任务书上所给系统与线路及所有负荷的参数,分析负荷发展趋势。从负荷增长方面阐明了建站的必要性,然后通过对拟建变电站的概括以及出线方向来考虑,并通过对负荷资料的分析,安全,经济及可靠性方面考虑,确定了110kV、35kV、10kV以及站用电的主接线,然后又通过负荷计算及供电范围确定了主变压器台数,容量及型号,同时也确定了站用变压器的容量及型号;最后,根据最大持续工作电流及短路计算的计算结果,对高压熔断器、隔离开关、母线
原创力文档

文档评论(0)