MiniCAS II
SUPERVISION RELAY
TECHNICAL DATA
Flygt MiniCAS II is a supervision relay for temperature On the front, there are three indication lamps, one for
and leakage sensors. It is designed for the Flygt 3000 supply, one for temperature alarm and one for leakage
pumps up to model 3300 and for the Flygt mixer program. alarm. For the communication between the pump and
There are three types of sensors that can be con- the MiniCAS II, only two wires are needed. The
nected to the MiniCAS II: Thermal switches, the CLS MiniCAS II is designed to be connected to a standard
water-in-oil sensor and the FLS sensor for leakage 11-pin socket.
detection in the stator housing. MiniCAS II is interchangeable with the original version
The sensors can be used in any desired combination. of MiniCAS.
For “Ex” certified pumps only combinations involving
thermals and FLS may be used.
Operational principle: Current Sensing
Approvals: CE, C-UR (covering USA and Canada)
Environment: 0–50°C. maximum 90% relative humidity
Supply voltage: 20-30 VAC (50-60Hz)
23.5–30 VDC
Relay contact rating: 250 VAC / 8A
Voltage to sensor: 12 VDC +/-5%
Values of operation: 3mA I 22mA = OK condition
I 3mA = High Temperature (or interruption)
I 22mA = Leakage (or short circuit), delay 10 sec.
(I = current measured by MiniCAS II)
Power supply required: 5 VA
OPERATION
Leakage: Changeover contacts 11–8 Normall