MiniCAS II SUPERVISION RELAY TECHNICAL DATA Flygt MiniCAS II is a supervision relay for temperature On the front, there are three indication lamps, one for and leakage sensors. It is designed for the Flygt 3000 supply, one for temperature alarm and one for leakage pumps up to model 3300 and for the Flygt mixer program. alarm. For the communication between the pump and There are three types of sensors that can be con- the MiniCAS II, only two wires are needed. The nected to the MiniCAS II: Thermal switches, the CLS MiniCAS II is designed to be connected to a standard water-in-oil sensor and the FLS sensor for leakage 11-pin socket. detection in the stator housing. MiniCAS II is interchangeable with the original version The sensors can be used in any desired combination. of MiniCAS. For “Ex” certified pumps only combinations involving thermals and FLS may be used. Operational principle: Current Sensing Approvals: CE, C-UR (covering USA and Canada) Environment: 0–50°C. maximum 90% relative humidity Supply voltage: 20-30 VAC (50-60Hz) 23.5–30 VDC Relay contact rating: 250 VAC / 8A Voltage to sensor: 12 VDC +/-5% Values of operation: 3mA I 22mA = OK condition I 3mA = High Temperature (or interruption) I 22mA = Leakage (or short circuit), delay 10 sec. (I = current measured by MiniCAS II) Power supply required: 5 VA OPERATION Leakage: Changeover contacts 11–8 Normall