SF6 开关检修工艺
SF6开关检修工艺
目 次
前言
1 范围 ·············································································································1
2 引用标准 ·······································································································1
3 110KV LW14-110 SF6 断路器 ··············································································1
4 LW6-110 SF6 断路器 ·························································································4
5 220KV-220 SF6 断路器 ······················································································6
6 LW2C-220 SF6 断路器 ·······················································································8
7 LWLL-110/3150-40 型断路器检修周期及检修项目 ·················································13
1
SF6 开关检修工艺
前 言
SF6高压断路器是电力系统中关键的控制和保护设备。电气设备的可靠性,而且用量大面
广。 SF6断路的可靠性,是电力系统安全与否的重要因素之一。 SF6断路器的可靠性关键在于
产品的制造质量和技术性能,但同时亦依赖于运行检修部门的维修质量。因此,加强检修管
理,提高检修质量,是保证高压断路器安全运行的关键。
近年来随着断路器的无油化不断发展,我局已大量地选用了 SF6断路器。但电力部至今无
统一标准的检修工艺。为了提高检修工艺水平,保证检修质量。有必要对该类设备的检修周
期,检修项目及质标准作统一的要求,特制订本规程。
本规程适用我局目前在运行的 SF6断路器而制订。 主要参考生产厂家说明书及兄弟局检
修工艺规程。由于 SF6高压断路器仍在不断改进与完善,加上我们水平低。如发现本规程与厂
家说明书有抵触之处,应以厂家新说明书为准。今后,如电力部颁发正式规程,则与部颁规
程为准。
2
SF6 开关检修工艺
1 范围
本标准规定了我局目前现有 SF6 开关维护,检修。其它型号参照执行
2 引用标准:
根据我省的具体条件制定主要考虑设备生产厂家的设备安装使用说明书和电力技术标准
中的部分标准以及国电公司标准.
3. 110KV LW14-110 SF6 断路器【西安高压开关厂】
3.1 检修周期和检修项目
3.1.1 检修周期
3.1.1.1 大修周期: 20年
3.1.1.2 小修周期:每年一次
3.1.1.3 临时性检修:
⑴ 小电流开断约 4000 次操作;额定电流开断 2000次操作或额定短路电流开断