QUESTION:
How can I set up a PROFIBUS FMS connection between WinCC and a KlöcknerMöller
controller?
ANSWER:
On the WinCC computer you must use ComProfibus to create an *.ldb file. Pay attention
here to the data for the KlöcknerMöller controller. In this c ase it is only possible to set up an
acyclic connection to WinCC. With respect to the KlöcknerMöller control, this leaves only 2
options open to parameterize a connection.
In the example here we have selected the CR 4 from the KlöcknerMöller data.
Set the following in ComProfibus:
ComProfibus
FMS M