Document Update PowerFlex 400 Firmware Release Number 4.xx Reference This document updates the PowerFlex 400 User Manual, Publication 22C-UM001D-EN-P dated August 2005 for compatability with Firmware Release Number (FRN) 4.xx. The latest PowerFlex 400 User Manual is available online at /literature New Parameter The following parameter has been added to the PowerFlex 400 Advanced Program Group with the release of FRN 4.xx. A200 [Motor NP FLA] Related Parameter(s): A167 Set to the motor nameplate rated full load amps. Values Default: Drive Rated Amps Min/Max: 0.1/(Drive Rated Amps × 2) Display: 0.1 Amps Related Parameter The following parameter is affected by the value set in parameter A200 [Motor NP FLA]. A167 [Flying Start En] Related Parameter(s): A200 Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM. Important: When this parameter is enabled, verify that A200 [Motor NP FLA] is set to the motor’s actual full load amp value. Options 0 “Disabled” (Default) 1 “Enabled” *T3I0* 5011638400-T3I0 Publication 22C-DU001A-EN-P – November 2005 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in Taiwan.