Application Note Setting the PCD to Trip on an Overvoltage Condition and Reclose When the Voltage Level Returns to Normal By Timothy Fahey, P.E. Note: The settings in this application note are shown as an example only. It is the user’s responsibility to determine proper settings and perform proper testing and validation for a given application. Scope: This application note applies to CPU Type 1 (firmware version 1.6 and later) and all Type 2 (current model) CPUs. This function permits the PCD to trip the recloser if an overvoltage condition exists on any o