(Feb 2003)
LIGHTNING PROTECTION INSTALLATION
GENERAL SPECIFICATION
1. SATISFACTORY INSTALLATION
The whole of the installation shall be carried out in accordance with:
(a) The latest S.A.B.S. Code of Practice for the Protection of Structures against Lightning - S.A.B.S. 03
; SABS IEC 61024 (1) , 61024 (1 -1); SABS IEC 61312 (1) ; SABS IEC 61662 NRS 042.
(b) The KwaZulu-Natal Department of Works General Electrical Specification.
(c) The Municipal By-Laws and any other special requirements as deemed necessary by the Local
Supply Authority;
(d) Local Fire Regulations.
2. S.A.B.S. APPROVED DRAWINGS
SABS Approved drawings are not required for this project.
3. TEST ON COMPLETION
Upon completion of the lightning protection system, the following tests shall be witnessed by an appointed
representative of the Employer. The results shall be recorded on suitable test certificates which must be
signed by both the Contractor and the Employers representative. A sketch must be included on each test
certificate indicating the positions of each earth electrode in relation to some permanent reference point. It
must also indicate the positions at which tests were carried out, the type of test and the results of these
tests.
3.1 Earth Resistance Test
The Earth Resistance Test shall involve measuring the resistance to earth of each rod-type
electrode, or group of rod-type electrodes, or trench earth which would normally be connected to one
down-conductor or earth terminal. This test must be made with the electrodes completely
disconnected from any part