- 1、本文档共15页,可阅读全部内容。
- 2、原创力文档(book118)网站文档一经付费(服务费),不意味着购买了该文档的版权,仅供个人/单位学习、研究之用,不得用于商业用途,未经授权,严禁复制、发行、汇编、翻译或者网络传播等,侵权必究。
- 3、本站所有内容均由合作方或网友上传,本站不对文档的完整性、权威性及其观点立场正确性做任何保证或承诺!文档内容仅供研究参考,付费前请自行鉴别。如您付费,意味着您自己接受本站规则且自行承担风险,本站不退款、不进行额外附加服务;查看《如何避免下载的几个坑》。如果您已付费下载过本站文档,您可以点击 这里二次下载。
- 4、如文档侵犯商业秘密、侵犯著作权、侵犯人身权等,请点击“版权申诉”(推荐),也可以打举报电话:400-050-0827(电话支持时间:9:00-18:30)。
查看更多
外文翻译--冷弯型钢框架结构设计方法.doc
PRESCRIPTIVE METHOD FOR RESIDENTIAL COLD-FORMED
STEEL FRAMING
Second Edition
Prepared for
The U.S. Department of Housing
and Urban Development
Office of Policy Development and Research
Washington, DC
Co-Sponsored by
The American Iron and Steel Institute
Washington, DC
and
The National Association of Home Builders
Washington, DC
by
NAHB Research Center, Inc.
400 Prince Georges Boulevard
Upper Marlboro, MD 20774-8731
August 1997
CONTENTS
5.0 STEEL FLOOR FRAMING 21
5.1 Floor Construction 21
5.2 Floor to Foundation or Bearing Wall Connection 21
5.3 Allowable Joist Spans 21
5.4 Joist Bracing 21
5.5 Floor Cantilevers 22
5.6 Splicing 22
5.7 Framing of Floor Openings 22
5.8 Floor Trusses 22
5.0 STEEL FLOOR FRAMING
5.1 Floor Construction
Cold-formed steel framing members shall comply with the provisions of Section 2.0. Steel floors shall be constructed in accordance with this section and Figure 5.1.
5.1.1 Applicability Limits
The applicability limits of Section 1.3 and Table 1.1 shall apply.
5.1.2 In-Line Framing.
Load bearing steel floor framing, wall framing, and ceiling/roof framing shall be constructed in-line with the vertical load bearing members (i.e. studs) located below. A maximum tolerance of 3/4 inch (19 mm) between the centerlines of the in-line members shall be permitted in accordance with Figure 1.2.
5.2 Floor to Foundation or Bearing Wall Connection
Cold-formed steel floor framing shall be anchored to foundations, wood sills, or load bearing walls in accordance with Table 5.1 and Figures 5.1 through 5.10. Fastening of steel joists to other framing members shall be in accordance with Table 5.2.
5.3 Allowable Joist Spans
The clear span of cold-formed steel floor joists shall not exceed the limits set forth in Table 5.3 for single spans and Table 5.4 for multiple spans. When continuous joist members are used for multiple spans, the interior bearing supports shall be located within two feet (0.6 m) of mid-span of the steel joists, and the
您可能关注的文档
- 基于ZigBee和LabView的多点无线温湿度采集系统设计.doc
- 基于ZigBee技术的远程医疗监护系统设计.doc
- 基于单片机和CAN总线的企业现场信息监控系统.doc
- 基于单片机城市十字口交通灯毕业论文设计.doc
- 基于单片机控制的交通灯带程序.doc
- 基于单片机控制的人体健康监测系统设计.doc
- 基于单片机控制的教学实验信号源发生器的设计.doc
- 基于单片机控制的智能窗的设计.doc
- 基于单片机控制的矩阵键盘显示系统设计.doc
- 基于单片机控制红外报警系统毕业设计(新鲜版).doc
- 市科技局副局长在理论学习中心组学习2025年全国两会精神研讨发言材料.docx
- 在深入贯彻中央八项规定精神学习教育读书班开班式上的讲话1.docx
- 关于开展深入贯彻中央八项规定精神学习教育的工作方案.docx
- 市国资委党委书记学习2025年全国两会精神专题研讨发言材料.docx
- 在2025年作风建设专题“读书班”上的研讨发言材料(八项规定).docx
- 在县政府全体会议暨廉政工作会议上的讲话4.docx
- 关于我市农村电商发展情况的调研报告.docx
- 在某某区安全生产重点工作安排部署会上的讲话.docx
- 市发改局党组书记在理论学习中心组会上学习2025年全国两会精神的研讨发言材料1.docx
- 商务局委员会(商务局)基层党组织“分类指导、争先进位”工作方案.docx
文档评论(0)