Reinforcement
7.5 STRUCTURAL SYNTHETIC FIBRES demonstrate the performance of synthetic structural fibres in
practice (see Section 9.4.3).
It is necessary to distinguish between the short polypropylene
micro fibres and the larger synthetic fibres being developed 7.6 REINFORCEMENT SPACERS AN D
for structural benefits similar to steel fibres.
CHAIRS
Polypropylene micro fibres used at typical dosages of 0.9
kg/m3 do not provide any significant post-first-crack duc- It is important that reinforcement is securely located in the
tility, as defined and measured by Japanese Standard test position required by the designer or its effectiveness may be
method JSCE-SF4 (40). Therefore they do not fulfil any
severely reduced. Chairs for supporting reinforcement are
structural role, as would steel fibres with proven structural manufactured from concrete, plastic or steel. Chairs suitable
performance. for ground-supported slabs are designed to prevent punc-
Structural synthetic fibres are larger and used at significantly turing of the membrane or sinking into the sub-base. Spacers
higher dosages than polypropylene microfibres. (See Section and chairs and their use should be in accordance with BS
11.6.) As with steel fibres,