无需互联通信的直流微电网实时功率协调控制策略.pdf
第39 卷 第12 期 电 网 技 术 Vol. 39 No. 12
2015 年12 月 Power System Technology Dec. 2015
文章编号:1000-3673 (2015 )12-3449-08 中图分类号:TM 72 文献标志码:A 学科代码:470 ·40
无需互联通信的直流微电网
实时功率协调控制策略
欧阳丽,周丽红,何海斌
(上海电气集团股份有限公司中央研究院,上海市 闸北区 200071 )
Real-Time Power Coordinated Control Strategy for DC Microgrid Without Communication
OUYANG Li, ZHOU Lihong, HE Haibin
(Central Research Institute of Shanghai Electric Group Ltd., Zhabei District, Shanghai 200071, China)
ABSTRACT: DC microgrid is usually connected to AC power 流负荷的典型低压直流微电网中,通过 Matlab-Simulink 仿
system through bidirectional DC-AC converter, controlling DC 真和实验结果验证了所提控制方法的有效性。
bus voltage constant and maintaining power balance. If only
关键词:直流微电网;直流母线电压;无互联通信;自适应
relying on upper-level centralized energy management system,
下垂;即插即用
DC microgrid cannot achieve real-time power balance and
DOI :10.13335/j.1000-3673.pst.2015.12.018
coordinated control in case of losing power balancing unit
caused by AC system fault, DC-AC converter operating in 0 引言
current limiting mode or even dropping out, leading to system
以微电网形式集成光伏、风机等可再生能源系
collapse and unstable operation. Therefore, a real-time power
统、储能单元和本地负荷,可有效提高配电网接纳
coordinated control strategy for DC microgrid without
communication is proposed. With this strategy, any unit in 分布式电源能力、增强负荷侧需求响应灵活性、改
[1-3]
system can switch its co