Measuring and Controlling of Analog signal Based on High-speed I/O port of PLC
Frequency signal is gotten from voltage signal by external V/F converter, and then is sent to high-speed counter of PLC. As a host, CPU222 of Siemens S7-200 series PLC is used. Through programming PLC, input voltage is measured by high-speed I/O channels. High-speed digital pulse of variable duty cycle produced by PLC’s PWM pulse generator is turned into voltage signal of amplitude-adjustable after external RC low-pass filter circuit filter to achieve controlling of output analog. The method reduces the