Method 1: Save as L5K format, modify L5K in text editor and attempt to re-import into a previous release. The following is an example of reverting a ControlLogix version 15 project back to ControlLogix version 13. 1). Open the v15 ACD file with RSLogix 5000 software and SAVE AS selecting the L5K format. Then close the ACD. 2). Once the L5K file is created, use the Windows Explorer to browse to its location on the hard drive. Then double click the L5K file and it will open up with a text editor such as NOTEPAD. 3). The L5K file contains at least three details requiring change. (example below) I