欧规(iec标准)与美规(ul标准)保险管熔断时间表

欧规 IEC标准 与美规 UL标准 保险管熔断时间表: 一. 快熔断 美规 UL标准 .. ELECTRICAL CHARACTERISTICS: Inf or If 110% of In 135% of In 200% of In In Min. Max. Max. 50mA – 6.3A 4 hrs 60min 2min In Rated Current, If Fusing Current, Inf Non-Fusing Current Pre-arcing time/current characteristics at Ta 23 C 欧规 IEC标准 ELECTRICAL CHARACTERISTICS: Inf or If 150% of In 210% of In 275% of In 400% of In 1000% of In In Min. Max. Min. Max. Min. Max. Max. 32mA – 100mA 60min 30min 10ms 500ms 3ms 100ms 20ms 125mA – 10A 60min 30min 50ms 2s 10ms 300ms 20ms In Rated Current, If Fusing Current, Inf Non-Fusing Current Pre-arcing time/current characteristics at Ta 23 C 二.慢熔断 美规 UL标准 ELECTRICAL CHARACTERISTICS: Inf or If 110% of In 135% of In 200% of In In Min. Max. Max. Min 80mA - 3A 4 hrs 60min 120s 5s 3.15A – 10A 4 hrs 60min 120s 12s In Rated Current, If Fusing Current, Inf Non-Fusing Current Pre-arcing time/current characteristics at Ta 23 C 欧规 IEC标准 ELECTRICAL CHARACTERISTICS: Inf or If 150% of In 210% of In 275% of In 400% of In 1000% of In In Min. Max. Min. Max. Min. Max. Min. Max. 50mA – 100mA 60min 2min 200ms 10s 40ms 3s 10ms 300ms 125mA – 20A 60min 2min 600ms 10s 150ms 3s 20ms 300ms In Rated Current, If Fusing Current, Inf Non-Fusing Current Pre-arcing time/current characteristics at Ta 23 C