- 1、本文档共18页,可阅读全部内容。
- 2、原创力文档(book118)网站文档一经付费(服务费),不意味着购买了该文档的版权,仅供个人/单位学习、研究之用,不得用于商业用途,未经授权,严禁复制、发行、汇编、翻译或者网络传播等,侵权必究。
- 3、本站所有内容均由合作方或网友上传,本站不对文档的完整性、权威性及其观点立场正确性做任何保证或承诺!文档内容仅供研究参考,付费前请自行鉴别。如您付费,意味着您自己接受本站规则且自行承担风险,本站不退款、不进行额外附加服务;查看《如何避免下载的几个坑》。如果您已付费下载过本站文档,您可以点击 这里二次下载。
- 4、如文档侵犯商业秘密、侵犯著作权、侵犯人身权等,请点击“版权申诉”(推荐),也可以打举报电话:400-050-0827(电话支持时间:9:00-18:30)。
查看更多
济南市某办公楼调用制冷机房设计说明书_secret
目 录
一.原始资料······················································3
1.1室外气象参数·····················································3
1.2冷负荷···························································3
1.3建筑材料·························································3
二.确定冷水机组的型号、台数··································3
三.冷却水系统设计··············································5
3.1冷却塔型号、台数的确定···········································5
3.2冷却水泵型号、台数的确定·········································6
3.3冷却水系统各管段管径的确定·······································7
3.4水处理设备确定···················································8
四.冷冻水系统设计···············································9
4.1集水器和分水器管径、官长的确定···································9
4.2冷冻水泵型号、台数的确定·········································10
4.3冷冻水系统各管段管径的确定·······································10
4.4膨胀水箱的选型···················································11
4.5水处理设备的确定·················································11
五.制冷机房布置··················································12
5.1技术要求·························································12
5.2建筑布置要求·····················································12
5.3设备安装设计····················································12
5.4设备的隔振与降噪················································13
六.设备明细表···················································14
七.设计总结······················································15
八.参考文献······················································15
济南市某办公楼空调用制冷机房设计
设计题目:济南某办公楼空调用制冷机房设计,总建筑面积12500㎡。冷冻水出水温度7℃,回水温度12℃。
一.原始资料
1地点:山东省济南市
济南市:北纬36.6°,东经117°,海拔170.3m。
1.2室外气象参数
夏季室外气象参数 冬季室外气象参数 夏季空调室外计算
干球温度 34.8℃ 冬季空调室外计算
干球温度 -7.7℃ 夏季空调室外计算
湿球温度 27℃ 冬季空调室外计算相对湿度 45﹪ 夏季空调室外平均风速 2.8m/s 冬季空调室外平均风速 2.8m/s 夏季大气压力 997.3hPa 冬季大气压力 101.9hPa 1.3冷负荷
本建筑物的总建筑面积为12500㎡,根据《空气调节技术》书中《国内部分建筑空调冷负荷指标的统计值》查的:办公楼的冷负荷指标(W/㎡):90-140 W/㎡。
《国内部分建筑空调冷负荷指标的统计值》中注明:当建筑物的总建筑面积在小于5000㎡取上限值,大于10000㎡时,取下限值。按建筑空调冷负荷指标确定的冷负荷即是制冷剂容量,不必再加系数。由于本建筑物的总建筑面积为8000㎡,所以,在此我们选用90 W/㎡。
则:本设计
文档评论(0)