1、粗格栅 栅前流速取0.6m/s,栅前水深根据最优水力断面公B=2h===0.88m,则h=0.44m,过栅流速取v=0.7m/s,栅条间隙e=20mm,格栅的安装倾角为60°,则栅条的间隙数为: n=Qmax*sinа0.5/ehv =0.23*(sin60°)0.5/(0.02*0.44*0.7) =34.7 n取38 栅槽宽度:取栅条宽度为S=0.01 m,取进水栅槽宽0.8m,一般栅槽比格栅宽0.2-0.3m,取0.2m, B=S*(n-1)+e*n+0.2 =0.01*(38-1)+0.02*38+0.2=1.33m,即槽宽为1.33m,取1.3m则 栅槽总长度: L=L+L+1.0+0.5+, L==(1.33-0.8)/(2*tg20°)=0.73m L= L/2=0.37m H=h+h=0.4+0.3=0.7m 则, L=L+L+1.0+0.5+ =0.73+0.37+1.0+0.5+0.7/tg60°=3.0m 每日栅渣量:(单位栅渣量取W=0.05 m栅渣/10 m污水) W=Qmax* W1*86400/(K总*1000) =0.23*0.05*86400/1*1000 =1.0m3/d 0.2 m3/d 宜采用机械清渣方式 栅槽高度: H=h+h1+h=0.4+0.1+0.3=0.8m 2、细格栅设计: 设栅前水深h=0.4m,进水渠宽度B=2h=0.8。过栅流速取v=0.8m/s,栅条间隙e=10mm,格栅的安装倾角为60°,则 栅条的间隙数为: n=Qmax·sinа0.5/ehv =0.23*(sin60°)0.5/(0.01*0.4*0.8) =66.84 n取67 栅槽宽度:取栅条宽度为S=0.01 m B=S*(n-1)+e*n+0.2 =0.01*(67-1)+0.01*67+0.2 = 1.53m 取1.50m 进水渠道渐宽部分长度: L= (B- B)/2tg=(1.53-0.8)/2tg20°=1.0m —进水渠展开角,B=B—栅槽总宽,B—进水渠宽度。 栅槽与出水渠连接渠的渐宽长度: L= L/2=1.0/2=0.5m 过栅水头损失: 设栅条为矩形断面,h=k*ξ*v *sin /2g k—系数,格栅受污物堵塞后,水头损失增大的倍数,取k=3; v—过栅流速; ξ—阻力系数,与栅条断面形状有关,ξ=(s/e),当为半圆形的矩形断面时,=1.83。 代入数据得:h=1.83*(0.01/0.01)*0.8*sin60°/(2*9.81) =0.05m 为避免造成栅前涌水,故将栅后槽底下降h作为补偿。 栅后槽总的高度: 取栅前渠道超高为h2=0.3 (m),栅前槽高H1=h+h2=0.7 m H= h1+h+h2=0.05+0.4+0.3=0.75m 栅槽总长度: L= l2+l1+0.5+1.0+ H1/tg60° =0.5+1.0+1.0+0.5+0.7/tg60° =3.4m 每日栅渣量:取W1=0.08 m3/(103*m3) W=Qmax* W1*86400/(K总*1000) =0.23*0.08*86400/(1*1000) =1.59 m3/d 0.2 m3/d 宜采用机械清渣方式 粗格栅和细格栅采用FHG-1.2-0.8,FHG-1.5-0.75型号格栅除污机。江苏天河FHG型反捞式格栅除污机 集水井及泵房 1、粗格栅后集水池容积 按停留时间10min计算得: V=500/60*10=80m3,取有效水深3.0m,则集水池面积为A=V/H=80/3.0=27㎡ 20000/24=834m3/h,选择三台流量的水泵,两用一备 曝气沉砂池后集水池 按停留时间10min计算得: V=500/60*10=80m3,取有效水深3.0m,则集水池面积为A=V/H=80/3.0=27㎡ 20000/24=834m3/h,选择三台流量的水泵,两用一备 细格栅后提升泵房 L*B*H=4.5*3*3,加1.5吨电动葫芦,行车轨道。 二沉池配水井 设进水管内流速v=0.8m/s,则管径D=(834/3600/0.8/0.785)1/2=600mm 设停留时间为t=5min,则配水井有效容积v=20000*5/24/60=70m3,采用圆形,有效水深3.0m,则A=23.3,r=2.7m。 设一根进水管,两根出水管,则出水管径d=(834/3600/0.8/2/0.785)

文档评论(0)

1亿VIP精品文档

相关文档