IBM AS400 Solution
APC Supported Solution for IBM AS/400 Servers using native controlled shutdown.
Step 1:
Cable // Triple Chassis: Use APC’s AS400 Interface Kit simple signalling cable part no. # 940-0006A or 940- 0031A “ This cables may be used in conjunction with different OS and AS400 ) and connect the cable to the triple chassis AP9604S. ( A 9 to 15 pin cable ( 940-0006A) and 9 to 9 pin cable (940-0031A) are included with the kit.)
Step 2:
Cable connection: Connect the cable end labelled UPS to the UPS and the other end to the AS/400.
Once this is done there should be a message on the AS 400 monitor that a UPS has been attached to the AS/400.
Step 3:
Settings: There are only two settings you can change on the AS/400 native UPS application:
3.1 Set the QUPSDLYTIM to a numeric value. This numeric value is your delay time before the AS/400 begins saving main storage and completes a shutdown. Although this is the best solution, you must determine how long time it takes for the system to complete a shutdown using PWRDWNSYS *IMMED. Once this value is determined, you can set the delay time to provide sufficient runtime without reaching low battery during the shutdown process.
3.1 If timing a PWRDWNSYS *IMMED is not possible, you could use this rough estimate to calculate shutdown time.
# Seconds = (2.816 * (Main Storage in Megabytes)) + 30
3.2 You can set the QUPSDLYTIM to *NOMAX. This allows the system to wait until low battery. This function is designed to allow third party software to initiate shutdown (Power Chute for AS/400). This is not the best solution since the system will wait until low battery to initiate the shutdown. Although you could extend the low battery duration on the a smart ups matrix or Symmetra to 10 minutes in order to allow a complete shutdown, you expose the AS/400 to an immediate shutdown upon IPL during successive power outages.
3.3 The triple chassis can be used
您可能关注的文档
最近下载
- 英语搞笑短剧剧本(6角色).docx VIP
- 实验班提优大考卷二年级上册语文人教版.pdf
- 小数乘除法竖式计算题500道及答案.docx VIP
- 655-诊断学与病理学-扬州大学2023年硕士研究生初试试卷.doc VIP
- 扬州大学 655诊断学与病理学 2021年考研真题.pdf VIP
- 非煤矿山标准化操作规程.pdf
- XAQ06 工程线施工安全监理实施细则(和若铁路J4标)2020.9.17.pdf
- 外研版英语 八年级上册 Module 5 Lao She Teahouse 单元整体教学设计.docx
- QC成果提高钢结构厂房防火涂料施工质量.ppt
- ninebot九号电动滑板车MaxG2说明书用户手册.pdf
文档评论(0)