SECTION 22 67 13 – HIgh purity water systems (RO) GENERAL RELATED DOCUMENTS Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section. Specifications throughout all Divisions of the Project Manual are directly applicable to this Section, and this Section is directly applicable to them. SUMMARY The water conditioning system/supplier shall be totally responsible for the supply and installation of the water treatment system to include the central RO water system, the building supply and return loop system, the final connection to the RO water outlet and quality assurance/quality controls of the entire system to assure meeting quality standards for CAP/NCCLS reagent water Specifications Type III at the point of use. The system/supplier shall guarantee that the water quality coming from the central system is the same quality at any point of use in the RO water loop system at initial start-up. Provide an RO system with capacities and electrical characteristics as scheduled on Contract Drawings. Scheduled gallons per day (24 hour period) shall be based on a feed water temperature of 77 degrees F. Provide complete system as manufactured by Marlo, Osmonics or Ionpure. REFERENCE STANDARDS The latest published edition of a reference shall be applicable to this Project unless identified by a specific edition date. All reference amendments adopted prior to the effective date of this Contract shall be applicable to this Project. All materials, installation and workmanship shall comply with the applicable requirements and standards addressed within the following references: 2015 Edition of the International Plumbing Code. Texas Water Code Chapter 37 Texas Health Safety Code Chapter 341 Title 30 Texas Administrative Code, Chapter 30, Subchapter H Underwriters Laboratories Listings. 2011 Edition of the National Electric Code ASME - Boiler and Pressure Vessel Code. ASTM D 3222 - Standard Specif

您可能关注的文档

文档评论(0)

bgl001 + 关注
实名认证
内容提供者

该用户很懒,什么也没介绍

1亿VIP精品文档

相关文档