- 1、本文档共12页,可阅读全部内容。
- 2、原创力文档(book118)网站文档一经付费(服务费),不意味着购买了该文档的版权,仅供个人/单位学习、研究之用,不得用于商业用途,未经授权,严禁复制、发行、汇编、翻译或者网络传播等,侵权必究。
- 3、本站所有内容均由合作方或网友上传,本站不对文档的完整性、权威性及其观点立场正确性做任何保证或承诺!文档内容仅供研究参考,付费前请自行鉴别。如您付费,意味着您自己接受本站规则且自行承担风险,本站不退款、不进行额外附加服务;查看《如何避免下载的几个坑》。如果您已付费下载过本站文档,您可以点击 这里二次下载。
- 4、如文档侵犯商业秘密、侵犯著作权、侵犯人身权等,请点击“版权申诉”(推荐),也可以打举报电话:400-050-0827(电话支持时间:9:00-18:30)。
- 5、该文档为VIP文档,如果想要下载,成为VIP会员后,下载免费。
- 6、成为VIP后,下载本文档将扣除1次下载权益。下载后,不支持退款、换文档。如有疑问请联系我们。
- 7、成为VIP后,您将拥有八大权益,权益包括:VIP文档下载权益、阅读免打扰、文档格式转换、高级专利检索、专属身份标志、高级客服、多端互通、版权登记。
- 8、VIP文档为合作方或网友上传,每下载1次, 网站将根据用户上传文档的质量评分、类型等,对文档贡献者给予高额补贴、流量扶持。如果你也想贡献VIP文档。上传文档
查看更多
ATVQATVQ推广手册(英文)
IP23 „Basic design“
Typical applications
HHP frequency inverter in an enclosure for installation in electrical
rooms
HHP frequency inverter in an enclosure for installation in
operating rooms with moderate dust exposure
Ambient temperature:
0...+40°C
(-10...+40°C with enclosure heating)
Ambient temperature up to +50°C with derating
Principle design
The fan of the power part, which is inside the device, provides the
forced cooling of the inverter and the heat abstraction of the
enclosure. The cooling air is supplied by a grill in the enclosure door
with large surface. For the air outlet, a cut-out in the roof sheet of the
enclosure is provided and an air guidance hood is mounted onto it.
The installation of the frequency inverter into the enclosure can be
realized with a DCL box at the top side of the inverter or with a line
reactor below the inverter.
1. Enclosure
2. Frequency inverter Altivar 61 or Altivar 71
3. DCL box (only available for 400V product lines)
4. Power part components (main switch, line contactor, chokes,…)
5. Air inlet grid (without filter mat) for control part and power part
6. Guided air flow (air channel) to avoid internal air short-cuts
7. Air guidance hood with splash water protection
Main parts of these cooling systems are the guided air flow inside the enclosure (air channel
between inverter/DCL box and the roof sheet of the enclosure) and the air guidance hood mounted
outside. On the one hand, an internal air short-cut is prevented and on the other hand the
specifications for IP 23 are fulfilled.
The air exchange takes place by the inlet grill (without filter mat!) in the enclosure door and the cut-
out in the roof sheet to the air guidance hood.
This cooling system does not need additional fans in the enclosure. The fan of the control part as
well as the fan of the power part inside the inverter provide the required air flow.
The forced cooling of the power part components, which is built-in below the inverter, is also very
ad