Short-CircuitCurrentRatings
Short-Circuit Current Ratings
Short-Circuit Current Ratings
Background
?
The 2008 NEC has a new definition of “short-circuit current Interrupting Rating
rating”. Previously there was no definition of short-circuit
current rating (sometimes referred to as “withstand rating”),
although it was referenced in several sections on the marking
and proper application of various types of equipment.
Because the term is referenced in multiple locations of the
Code, it was necessary to add a definition to Article 100 of
the NEC?.
Article 100 Definitions
Short-Circuit Current Rating. The prospective
symmetrical fault current at a nominal voltage to which an Normal Current Rating
apparatus or system is able to be connected without
sustaining damage exceeding defined acceptance criteria. Figure 2
What is Short-Circuit Current Rating? Interrupting rating is the maximum short-circuit current an
overcurrent protective device can safely interrupt under
Short-circuit current rating (SCCR) is the maximum short- standard test conditions; it does not ensure protection of the
circuit current a component or assembly can safely withstand circuit components or equipment. Adequate interrupting
when protected by a specific overcurrent protective device(s) rating is required per 110.9. The fuse in Figure 2 has a UL
or for a specified time. Adequate short-circuit current rating Listed interrupting rating of 300kA at 600Vac or less.
is required per 110.10.
When analyzing assemblies for short-circuit current rating,
both the interrupting rating of overcurrent pro
文档评论(0)