综合部分负荷性能系数IPLV与COP、APF的比拟(国外英文资料)
综合部分负荷性能系数IPLV与COP、APF的比较(国外英文资料)
IPLV definition
COP (coefficient of performance) nominal working condition of the coefficient of performance is under prescribed conditions, the refrigeration unit in the same units (hot) quantity divided by the total input power ratio are obtained.
PLV (part load value) part load performance coefficient is expressed in a single numerical air conditioning with partial load efficiency index of the chiller, it is based on the unit part load performance coefficient value, according to the unit under various load running time of the weighted factor calculated.
IPLV (integrated part load value) integrated part load performance coefficient is expressed in a single numerical air conditioning with partial load efficiency index of the chiller, it is based on the table under the provisions of the unit under part load performance coefficient IPLV condition, according to the unit under various load running time of the weighted factors, through the IPLV numerical formula.
Note: the above definitions are all based on the latest GB/T 18430.2-2008 standard.
The formula
IPLV/NPLV? The formula is as follows:
IPLV is a cross a plus b times b plus c times c plus d times d
Among them:
A = efficiency (COP, kW/kW) when the unit is 100%.
B = the efficiency of the unit 75% load
C = the efficiency of 50% of the unit load
D = the efficiency of the unit 25% load
A b c d
The cold region was 1.0% 32.7%, 51.2%, 15.1%
The cold region was 0.7% 36.2%, 53.4%, 9.8%
The temperature of the summer and winter cold was 2.3% 38.6% 47.2% 11.9%
The temperature of summer and winter was 0.7% 46.3%, 41.7% 11.3%
The national weighted average was 1.3%, 40.1%, 47.3%, 11.3%
(source: public building efficiency design standard (public building part))
Note 1: partial load percentage calculation is the nominal refrigerating quantity
Note 2: partial load performance factor IPLV represents the average operating condition of a single unit, and may not represent a specific project installa