判断电压电流互感器极性的新方法!
A new method for judging polarity of voltage and current transformer
[Abstract] the application of Kirchhoffs Law (Kirchhoffs Current Law) and the two circuit wiring principle, deduces a judgment of voltage and current transformer polarity of the new method, the detection method and the traditional comparison, proved its superiority and practicality, for the following reference and use care professionals.
Transformer, relay protection, Kirchhoffs Law (KCL), polarity
Introduction
Transformer and current transformer protection voltage and current isolation circuit one or two times two times one or two times in the relay circuit, their side has two or more terminals, either side of the terminal leads to wrong, phase change will make two side 180 degrees, not only affects the relay protection device correctly action, and affect the operation monitoring and accident treatment of power system, even endanger the personal safety and equipment. Therefore, it is very important to judge whether the polarity of transformer (voltage transformer) and current transformer is correct or not.
1 traditional polarity detection method
1.1 DC method
The traditional polarity detection method of voltage and current transformer can be connected to line by Figure 1. The dry battery and the magnetoelectric instrument with high sensitivity are used to measure the line. When the polarity is detected, the positive electrode of the battery is connected to the K end of the primary coil, and the positive end of the magnetoelectric meter (such as a pointer type ammeter or a voltmeter) is connected to the K end of the two coil. When the switch is closed when the S moment, the meter pointer bias right (positive), while the S switch disconnected instantly, the pointer is biased towards the left (reverse direction), indicates that the transformer one or two side terminals for polarity. On the contrary, for polarity.
1.2, exchange method
The transformer one or two coil end L2, K2 connec