防雷、接地施工工艺(国外英语资料)
防雷、接地施工工艺
(1) overview
Civil engineering lightning fortification is divided into three stages, the roof generally use 25 x 4 hot galvanized flat steel as lightning belt along the parapet around the laying of 25 x 4 hot galvanized flat steel lightning belt clip support spacing of 1 meters, but must be consistent, at the corner of the hanging segment is not more than 1 meters high, with lightning out of the house decoration or parapet 0.15 meters, while the roof adopted 25 * 4 hot galvanized flat steel components ranging from lightning grid. The lightning protection grid is laid along the roof, and all the metal components above the roof shall be welded with the lightning conductor.
At present, the general civil construction structure using the column or shear wall in the main reinforcement as the lead line, connected steel welding, diameter greater than 16 mm two as a group, at the top of the pillars embedded 100 * 100 * 8 steel, used to convert the main pillars of reinforcement and lightning protection belt connection.
The form of grounding is mainly man-made grounding body and using foundation as grounding form. The equipotential grounding network is made up of the steel net of the cap and the connection of the steel bar of the pile foundation, and the grounding resistance is no more than 1 ohms.
Each layer of building exterior wall continuous beam reinforced with welded steel floor form equalizing ring, and reliable line is connected with the lead, on the wall of metal doors and windows, metal structure, exterior wall railing and equalizing ring is connected to prevent thunder.
In recent years, equipotential bonding has become more and more strict, mainly including total equipotential bonding, auxiliary equipotential bonding and local equipotential bonding. Room, toilet equipment, metal pipelines and other common equipotential grounding.
(2) construction process
Construction preparation: earthing device installation, lead line installation, lightning protection t
文档评论(0)