CALCULATIONS FOR SHORT CIRCUIT (计算短路)
1. Geno P. PETER
CALCULATIONS FOR SHORT CIRCUIT WITHSTAND
CAPABILITY OF A DISTRIBUTION TRANSFORMER
1. DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING, LOYOLA INSTITUTE OF TECHNOLOGY AND SCIENCE
LOYOLA NAGAR , THOVALAI, TAMILNADU-629302, INDIA
ABSTRACT: During normal lifetime, transformers are submitted to a variety of electrical, mechanical and
thermal stresses. One of the most critical situations is that caused by external short circuits, which produces
high currents in the transformer windings and hence high internal forces in the windings. These forces are
potential sources for damaging transformers. In this paper the different parameters for short circuit
withstand capability of a transformer is calculated considering a 1500KVA, 22KV/415V, Dyn11 Distribution
Transformer. The short circuit withstand test of a Transformer cannot be performed in the Test Laboratory of
any manufacturer. There is a need for a high test field power, especially for large units with ratings of
100MVA and above. The tests can only be performed at a few powerful test stations, such as those operated
in KEMA (Netherlands), EDF (France), CESI (Italy) or IREQ (Canada) [1]. Short circuit tests are expensive. The
cost of the test itself is high. The cost also increases due to activities such as, transporting the transformer
under test from the factory, local installation at the test laboratory and again at the factory, untanking and
inspection, repetition of dielectric tests etc. For this reason the IEC standards also permits demonstration of
the short circuit ability using calculation and design considerations.
KEYWORDS: IEC, KEMA, EDF, CESI, IREQ
INTRODUCTION
The short circuit test is carried out to verify the integrity for stresses, primarily mechanical,
developed when short circuit current flows through the transforme
您可能关注的文档
- Brief Study on Domestication and Foreignization (简短的关于归化和异化的研究).pdf
- Briggs And Stratton Governor Repair Manual(布里格斯和斯垂顿州长维修手册).pdf
- Briggs Stratton 100212 Manual The Best PDF (布里格斯Stratton 100212手册最好的PDF).pdf
- Bridge Preservation Guide Federal Highway (桥保护指南联邦高速公路).pdf
- Bright Futures Student Handbook(明亮的期货学生手册).pdf
- brisket drofbbq(胸肉drofbbq).pdf
- Briggs Stratton 100212 Manual (布里格斯Stratton 100212手册).pdf
- BRITISH COLUMBIA SECONDARY SCHOOL (不列颠哥伦比亚中学).pdf
- British Orienteering Federation(英国越野识途比赛联合会).pdf
- British Society of Audiology and British Academy (英国社会的听力学和英国学院).pdf
文档评论(0)