LOW ZERO-SEQUENCE IMPEDANCES ON GENERATORS Date: August 30, 2000 Revision:0 Authors: Michael Simpson and John Merrell INTRODUCTION When considering the AIC rating of switchboards and other components, it is important to remember the source of the fault current and the nature of that source. In a recent study performed by Power Systems Engineering, a generator-fed switchboard was determined to be underrated due to line-to- ground fault magnitudes. The engineer specifying the equipment had used three-phase fault calculations to select the ratings for the equipment. DISCU