电力系统分析大作业-matlab三机九节点潮流计算报告推荐
电力系统分析大作业 一、设计题目本次设计题目选自课本第五章例5-8,美国西部联合电网WSCC系统的简化三机九节点系统,例题中已经给出了潮流结果,计算结果可以与之对照。取ε=0.00001 。二、计算步骤 第一步,为了方便编程,修改节点的序号,将平衡节点放在最后。如下图: 92132745683 第二步,这样得出的系统参数如下表所示: 第三步,形成节点导纳矩阵。 第四步,设定初值: ; ,。 第五步,计算失配功率 =0,=-1.25,=-0.9,=0,=-1,=0,=1.63, =0.85; =0.8614,=-0.2590,=-0.0420,=0.6275,=-0.1710,=0.7101。 显然,。 第六步,形成雅克比矩阵(阶数为14×14)第七步,解修正方程,得到:-0.0371,-0.0668,-0.0628,0.0732,0.0191,0.0422,0.1726,0.0908;0.0334,0.0084,0.0223,0.0372,0.0266,0.0400。从而-0.0371,-0.0668,-0.0628,0.0732,0.0191,0.0422,0.1726,0.0908; 1.0334,1.0084,1.0223,1.0372,1.0266,1.0400。然后转入下一次迭代。经三次迭代后。迭代过程中失配功率的变化情况如下表:k0123Δ=P10-0.01060.00