Example – High-impedance scheme Voltage setting: Above the maximum voltage for an external fault assuming that one CT saturates completely High enough so that pickup current is above the short circuit current on the secondary of any PT or station service transformer inside the bus zone Below the accuracy class voltage rating of the lowest accuracy class CT in the differential circuit Low enough so that pickup current is below the minimum fault current for the bus THANK YOU SUCCESS * * 可编辑 Example – High-impedance scheme CT requirements: CTs dedicated to bus protection (cannot be shared)