IOPFA (IRTFA) fault detection supervision adds security during external faults with CT saturation. The harmonic blocking element includes common or independent 2nd and 4th harmonic blocking and independent 5th harmonic Operating Region 2 blocking. P L S Volts/Hertz Elements 1 P L S The SEL-487E provides comprehensive volts/hertz (V/Hz) protection (24). The SEL-487E maintains 087P Restraining Region frequency tracking from 40.1 to 65.0 Hz when voltage inputs are provided to the relay. Two independent V/Hz IRTFA curves with definite and custom 20-point curve characteristics can be selected using programmable Figure 6 Adaptive Slope Differential Characteristics logic. Use the