800kV罐式断路器液压机构渗油的分析及对策
李海波
万荣兴
甘肃省电力公司检修公司 甘肃省 兰州市 730050
[摘 要]结合一起800kV罐式断路器液压机构渗油缺陷,认真分析机构组装工艺,并对机构零
部件进行了检查测试,发现连接套设计公差偏大、现场安装方法不当是引发缺陷的根本原因。通过重
新设计加工连接套、改进现场安装方法,彻底消除了机构存在的安全隐患,为后续800kV罐式断路器
安全运行奠定了基础。
[关键词]罐式断路器 ; 液压机构 ; 渗油
Analysis and Countermeasures to oil seepage fault of 800 kV pot breaks hydraulic mechanism
Li Hai-bo Wan Rong-xing
Gansu Electric Power Maintenance company, Lanzhou 730050
[ Abstract ] Combined with the 800kV pot breaker hydraulic mechanism oil seepage fault,the earnest
analysis hydraulic mecanismassemles a raft,carrid on checktest o hydaulicmechansm zeo
partses,discover conjunction parts tolerance bigger、 installing method inaccuracy is the root reason that cause
failures.Pass to re-design the conjunction parts and improvement to install a method,complete elimination the
security risk exists for follow-up to 800kV pot breaker went into operation basis.
[ Key words ] pot breakr ; ydrauic mehanism ; oi seepge falt