大学毕业设计论文-远方跳闸保护在终端变电所应用电气自动化论文

摘 要 随着国家城农网改造工作的不断深入,和扩大电力市场的需求。电网中改造和新建变电所逐渐增多,其中专供地区或厂矿的终端变电所占了很大部分。本文拟对远方跳闸保护在终端变电所应用进行可行性分析,以期达到完善保护性能,提高继电保护可靠性。以及适当地减少部分一次设备投资的目的。在改建或新建的终端变电所中,在供电侧和变压器之间加装一套远方跳闸保护,可以完善继电保护的性能,提高继电保护的可靠性。并且在充分满足了故障时继电保护可靠性的前提下,可以省去终端变电所内变压器高压侧的一组断路器。因此,无论从技术效益,还是经济效益方面考虑,都是一件值得重视的事情。 关键词: 远方跳闸 就地判别 线路变压器组 终端变电所 Abstract With the last developments of the reconstruct project of the country’s towns and rural areas net and the demands of expand electric power market. The reconstruct in the electric net and the new transformable electric station is gradually increasing. In the same time,the quantities of the transformable electric station of exclusive zone or factory also is increasing. As for the scarcity of protect configuration in the line transformer groups connection way,the article achieves the purposes of perfect performance,improving the reliability of relay’s protect and properly reducing parts once equipment investment via developing distance skip gate protector in the terminal transformable electric station’s application. In the rebuilding or new terminal transformable electric station,if adding to install a set of distance skip gate protector between power supply side and transformer,it may perfect the performance of relay’s protect,improve the reliability of relay’s protect and leave out a set of breaker of transformer’s high voltage side in the transformable electric station in the premise of sufficient satisfying the reliability of relay’s protect on a hitch. It is attach importance to technique benefits or economic benefits. Keywords: distance skip gate spot distinguish line transformer groups terminal transformable electric station 第1章 绪论 课题的意义 随着我国国民经济的飞速发展,对电力的需求增大,电网的规模不断扩大。在国家城网改造中,新建和改造了很多终端变电所。在变电所设计中,电气主接线的选择对运行的可靠性、灵活性和经济性起着决定性的作用。电气主接线直接影响着配电装置的布置、继电保护和自动装置的配置。而与此同时,电气主接线的选择也受到保护配置的限制和影响。对二次保护和自动装置的投资相对于电网一次投资而言更为经济,在一次系统接线方式能够满足要求而保护配置存在困难时,研究新的保护配置方法可以带来明显的经济效益。 在能满足运行要求的条件下,变电所高压侧宜采用断路器较少或不用断路器的接线。35~110kV线路

文档评论(0)

1亿VIP精品文档

相关文档