Calculation Sheet for Canopy of Undergroud Lobby
-Doha High Rise Office Building
King Glass Engineering Group
Calculated by: Checked by:
Architectural: Structural:
This calculation sheets should be read in conjunction with the related drawings.
1. Calculation of Perforated Al Sheet
The perforated Al sheet at the outermost of the canopy is the most critical one in press bearing and calculation is required. Relevant sketches are as follows:
Figure 1-1 Perforated Al Sheet Plan
Figure 1-2 Section A-A
Figure 1-3 Section B-B
Figure 1-4 Sample C
Figure 1-5 Sample D
Figure 1-6 Sample E
1.1 Calculation of Supporting Frame and Rinforcement Bar of Al Sheet
1.1.1 Design Sketch
Figure 1-6 Supporting Frame and Reiforcement Bar
The ‘▽’in the sketch symbolizes hinged connection.
Section of frame is as follows:
Figure 1-7 Frame Section
Section data of reinforcement bar is as follows:
Figure 1-8 Sectional Data of Reinforcement Bar
1.1.2 Standard Load
1.1.2.1 Standard Windload
This project is 100m from the coastline, which ground surface roughness is sorted as “Village”.
Building-type factor: Kb=2。(BS6399 part2-1.6.1 table 1)
Building height: H=1.3m300m,
Cr0.25,( BS6399 part2-1.6.1 table 1)
Effective height: He=1.3m
According to Section 2.2.2, part 5 of tender document for Doha High Rise Office Building, the basic wind speed Vb is 25m/s.
Site windspeed: Vs=Vb×Sa×Sd×Ss×Sp (BS6399-part 2-2.2.2)
Sa=1+0.001△s (BS6399-part 2-3.2.2)
In which::
Vb Sa Height factor
Sd Direction factor (Ref. BS6399, Clause2.2.2.3, Volume 2.)
Ss Season factor (Ref. BS6399, Clause2.2.2.4, Volume 2.)
Sp Propability factor (Ref. BS6399, Clause2.2.2.5, Volume 2.)
△s is the altitude of site ground surface.
△s=2m, So, Sa=1+0.001x2=1.002
Sd =1.0,Ss =1.0 ,Sp =1.0
∴ Vs=Vb×Sa×Sd×Ss×Sp=2