Frequency conversion factor
Proposed Frequency Conversion Factor Wording for C57.12.90
WG Loss Tolerance Measurement
Ed teNyenhuis WG Chair
Oct 25, 2005
Add to Annex A - Bibliography:
[B6] Ramsis S. Girgis, Barry Beaster, Ed G. teNyenhuis, “Proposed Standards for Frequency Conversion
Factors of Transformer Performance Parameters”, IEEE Transactions on Power Delivery, Pages 1262 –
1267, Vol. 18, No. 4, October 2003
New Section:
Annex B
(Normative)
Frequency Conversion of Measured Performance Parameters
While it is most preferred to perform all tests at the rated frequency, in the event it cannot be done at the
rated frequency, then upon mutual agreement with the customer at the tender stage or prior to a contract,
conversion factors given below shall be used to convert the measured values from the frequency used for
measurement to the required rated frequency. The purpose of the frequency conversion factors is to have
uniformity amongst the manufacturers when such cases arise. The below conversion factors are mainly
intended for 50Hz to 60Hz conversion, however similar 60Hz to 50Hz conversion is also described. The
60Hz to 50Hz conversion factors are essentially the reciprocal of the 50Hz to 60Hz values.
B1. No Load Loss Exciting Current
The following conversion factors shall be used to convert the values of measured no load loss and exciting
current at the design flux density from the frequency used for measurement to the required rated frequency.
Voltage measured according to the average voltmeter method should be applied such that the resulting core
flux density is equal to the flux density at the rated frequency of the transformer. For example, in the case
of the test performed at 50 Hz on a 60 Hz transformer, the applied voltage should be 5/6 of the voltage
corresponding to the 60 Hz operation.
No Load Loss Conversion Factors (50 Hz to 60 Hz):
Single Phase: B ≤ 1.4T = 1.32
B 1.4T = 1.32 - 0.05×(B-1.4)
Three Pha
您可能关注的文档
- EN-Scorecar-Mar-2012.pdf
- ENCOURAGING GENDER BALANCE A SURVEY OF EUROPEAN SCIENCE MUSEUM WEBSITES.pdf
- Endotracheal Tube Cuff Leaks.pdf
- Energy Efficiency General.pdf
- ENERGY EFFICIENCY OF GREEN ROOFS AND GREEN FACADES IN.pdf
- Energy efficiency of neptunium redox battery in comparison with vanadium battery-数学模型.pdf
- Energy Efficiency Requirement for Refrigerator_2014DOE_Haier_20130124.pdf
- Energy fluctuations and the ensemble equivalence in Tsallis statistics.pdf
- Energy-Calibration of the ATLAS Hadronic and Electromagnetic Liquid-Argon Endcap Calorimete.pdf
- Energy savings and speedups from partitioning critical software loops to hardware in embedd.pdf
最近下载
- 金刚石绳锯机的使用和维护要点讲解.doc
- 某县在全市利用外资工作汇报会上的发言材料--强势组织不放松 乘风乘势谋突破.doc VIP
- 2025年塔里木职业技术学院单招职业技能测试题库及完整答案1套.docx
- 小米汽车的营销策略研究.docx VIP
- sinoco西诺克SIN系列变频器调试参数设置故障代码资料.pdf VIP
- 流行歌曲口琴简谱集.doc
- 2025年格力空调分销渠道设计分析报告.pdf VIP
- 变革型领导对员工创新行为的影响分析-analysis of the influence of transformational leadership on employees' innovative behavior.docx
- 《放射化学基础》课件.ppt VIP
- 山西12J1工程用料做法(图集规范).pdf
文档评论(0)